Fire Rating
|
Specification |
Detail |
| 120 minutes |
8mm
TRILITE RMS board each side of 75mm galvanized steel studs
at 610mm centres with 75mm thick rockwool (60Kg/m3) in the
cavity. Screws are 250mm distance from each other, total wall
thickness =91mm.
|
 |
180
minutes |
12mm
TRILITE RMS board each side of 75mm galvanized steel studs
at 610mm centres with 75mm thick rockwool (60Kg/m3) in the
cavity. Screws are 250mm distance from each other, total wall
thickness = 99mm. |
 |
252
minutes |
Double
10mm TRILITE RMS board each side of 100mm galvanized steel
studs at 610mm centres with 75mm thick rockwool (60Kg/m3)
in the cavity. Screws are 250mm distance from each other,
total wall thickness = 140mm. |
 |
|
| |
 |
 |
 |
| Pre Test View: Fire Side |
Observation at 105 Minutes |
Observation at 120 Minutes |
 |
 |
 |
| Observation at 180 Minutes |
Post Test Observation: Fire Side Face |
Post Test Observation: Non Fire Side |
|
| |
|